Simplex 4098-9756 Addressable Duct Sensor Housings with TrueAlarm Photoelectric Sensor (ULC)
Simplex 4098-9756 Compact air duct sensor housing with clear cover to monitor for the presence of smoke** Includes factory installed TrueAlarm photoelectric smoke sensor and features:
- Individual sensor information processed by the host control panel to determine sensor status
- Digital transmission of analog sensor values via MAPNET II® or IDNet™, 2-wire communications
- Programmable sensitivity, consistent accuracy, environmental compensation, status testing, and monitoring of sensor dirt accumulation.
Model Simplex 4098-9756:
- Duct sensor housing with supervised output for multiple remote relays; requires separate 24 VDC includes one relay
- Relay output is under panel control
- At the panel, relay output can be activated manually or in response to a separate alarm or other input
Simplex 4098-9756 General features:
- UL listed to Standard 268A
- Clear cover allows visual inspection
- Test ports provide functional smoke testing accesswith cover in place
- Mounts to rectangular ducts or round ducts; minimumsize is 8” (203 mm) square or 18” (457 mm) diameter
- Magnetic test feature for alarm initiation at housing
- Optional weatherproof enclosure is available separately (refer to data sheet S4098-0032)