The Simplex 4905-9835 converts a steady-on 24 VDC notification appliance circuit into the Temporal Code 4 pattern used for carbon monoxide alarms, so a CO warning sounds different from a fire alarm. With its control NAC off, the outputs follow the fire signals on the input NAC.

  • Temporal Code 4 per NFPA 720: four 100 ms pulses, then 5 seconds off
  • Output NAC 24 VDC, up to 3 A, limited by the input NAC; audible appliances only
  • Up to 20 modules can share one control NAC; stand-alone mode for CO-only NACs
  • Works with 4007ES Hybrid, 4010ES, 4100ES, 4100U and 4009 IDNet NAC Extender sources
  • Mounts in a 4 in. square box; 18 to 12 AWG screw terminals
  • UL 864 and ULC S527 listed

Not for strobes or SmartSync horn-control appliances. The module must be close-nippled to the input NAC source, 20 ft (6 m) maximum.