The Simplex 4004-9302 is the 4004R suppression releasing panel in red, listed to UL 864 and ULC S527 for agent release and for deluge and preaction sprinkler control. Thirteen application modes cover single and dual hazard release, deluge and preaction.
- Four Class B initiating circuits, up to 30 detectors each, 3.3 kΩ end-of-line
- Two Class B NACs and two Class B releasing appliance circuits, 2 A each
- Two special-purpose monitoring circuits for manual release/abort or waterflow/supervisory
- 3 A supply at 25.5 VDC; charges batteries up to 12.7 Ah
- 120 VAC 60 Hz or 220/230/240 VAC 50/60 Hz, auto-select
- Release delay 0 to 30 seconds
- NEMA 1 and IP30 cabinet and door
Order separately: two 12 V batteries, one 2081-9046 coil supervision module per releasing circuit, and a maintenance switch. Class A wiring needs the 4004-9864 adapter.
| Brand | Simplex |
|---|---|
| Manufacturer part number | 4004-9302 |
| Product type | Fire Alarm Control Panels |
| Shipping weight | 1.0 lb |
| Condition | Brand new, factory sealed |
| Warranty | 1 year |
| Currency | Canadian dollars (CAD) |
Need a manual, listing or cut sheet that is not here? Email info@jemsystems.ca with the part number.
- Delivery across Canada in 2 to 4 business days.
- Free shipping on orders over $250 CAD.
- Returns within 30 days of the invoice date for unused items in original packaging, with an RMA number. Restocking fees may apply. See our refund policy.
- 1 year warranty on all products.
- Questions about an order? Email customerservicegroup@jemsystems.ca or call +1 909 235-5810.