Edwards SIGA-DTS Signature Duct Detector Test Station, Key Switch with Input Module, 2-Gang


Price:
Sale price$213.95 CAD
Stock:
Only 1 unit left

Availability

Mfr. part #: SIGA-DTSUPC: 793016021496
In stock: 1 availableReady to ship today
Delivery across Canada in 2 to 4 business daysFree shipping on orders over $250 CAD

Buying for a project or in bulk?Request a volume quote

Genuine stockBrand new, factory sealed
1 year warrantyOn every product
30 day returnsSee our return policy
Secure checkoutEncrypted payments
Need help with this part?Call +1 909 235-5810 or email info@jemsystems.ca
American Express Apple Pay Google Pay Mastercard PayPalShop Pay Visa

Frequently bought together

The Edwards SIGA-DTS is a Signature Series duct test station: a key switch with an integral intelligent input module on a two-gang plate. It lets a technician test a duct detector mounted out of reach above a ceiling from an accessible location.

  • Turning the key to TEST lights the LED and reports a duct detector test alarm, so programmed damper and smoke control sequences also run
  • Panel reset clears the test; the key cannot be removed in TEST
  • Occupies one module address on the Signature loop
  • 15.2 to 19.95 VDC (19 VDC nominal); 250 µA standby, 400 µA activated
  • White engineered plastic plate; two keys supplied (replacement key P-037449)
  • Mounts on a 2 in. deep two-gang or 4 in. square box (ordered separately)

Documented for SIGA-SDH and SIGA-SDHR duct housings. Relay bases are not operated automatically unless programmed at the panel.